BSM-WS36A Display

Baud Rate and Device Address

The currently set baud rate and device address is shown at the meter's display at the screen Zähleradresse/Device address in an encoded representation.

Device Address Screen

This data is presented in the form BB0AAA where BB is the baud rate index as given below and AAA the decimal value of the Modbus device address. The following baud rate indices BB are used:

Index Baud Rate
00 1,200 Bd
01 2,400 Bd
02 4,800 Bd
03 9,600 Bd
04 19,200 Bd
05 38,400 Bd
06 57,600 Bd
07 115,200 Bd
08 230,400 Bd
09 460,800 Bd
10 921,600 Bd

So the screen above shows baud rate index 04 (19,200 Bd) and device address 042 (42).